Skip to main content

Sakura Air Conditioner Error Codes

 

Sakura Air Conditioner Error Codes
Sakura Air Conditioner Error Codes

Content:

  1. Packaged Wall Through Air Conditioner
  2. Hydronic Cassette Air Conditioner
  3. Rooftop Package Air Conditioner

1-Packaged Wall Through Air Conditioner (for wall mounted & floor console) Model: SHW- 08R (cooling / heating)

Please check the following items before asking for repairing:

Error CodesSolution
E2Failure of the indoor sensor. Change the indoor temperature sensor.
E3Protection of cooling mode.
E4Failure of the indoor coil sensor. Change the indoor coil sensor.
E5Failure of the upper fan motor.
E6Failure of the system. Check if the refrigerant leaking or missing.
E7Protection of heating mode.

Error codes are for information only. Advise your local service agent as appropriate.

Troubleshooting

Problem: The unit does not work

  1. Cause: Power supply fault: 1. Not plugged in; 2. Faulty plug or socket; 3. Fuse broken
  2. Solution: 1. Plug in correctly; 2. Change the plug or socket; 3. Replace fuse

Problem: The unit stops running automatically

  1. Cause: 1. Timer is set or room temperature is lower than set temperature. 2. The water tank is full.
  2. Solution: 1. Close the timer or reset temp. 2. Drain off the water.

Problem: In cooling mode, no cooling air coming out

  1. Cause: 1. Room temperature is lower than set temperature. 2. There is frost on the surface of evaporator.
  2. Solution: 1. This is normal. 2. The unit is defrosting and it will run when the defrosting is finished.

Problem: The remote control does not work

  1. Cause: 1. Exhausted batteries 2. Batteries incorrectly installed.
  2. Solution: 1. Change the batteries. 2. Re-install the batteries correctly

Problem: The unit does not work for 3 minutes when switched on.

  1. Cause: Protection of the unit.
  2. Solution: Wait for approx.3 minutes and the unit will start.

2-Hydronic Cassette SFP – KM – DLY Series

When faulty slave unit is detected, unit display area shows the faulty unit address, time area shows the error code and backlight change to red color. Should there be multiple units having problems, they will be shown one after another.

Error CodesSolution
E2Indoor coil sensor 2 faulty (4 pipe unit)
E3Return air sensor faulty
E4Indoor coil sensor 1 faulty
E5Indoor coil low temperature protection
E6Indoor coil over heat protection
E7Water pump faulty
E8Local communication error
 Sakura Hydronic Cassette AC Remote Control
Sakura Hydronic Cassette AC Remote Control

Led lights of lamp board on unit panel & error display

For all units Red LED light

Heat ModeRed LED On
For master unit indicating defect status of all slave unit
Unit 2 failureBlink 2 times, stop 3 sec
Unit 3 failureBlink 3 times, stop 3 sec
Unit 4 failureBlink 4 times, stop 3 sec
Unit 5 failureBlink 5 times, stop 3 sec
Unit 6 failureBlink 6 times, stop 3 sec
Unit 7 failureBlink 7 times, stop 3 sec
Unit 8 failureBlink 8 times, stop 3 sec
Unit 9 failureBlink 9 times, stop 3 sec
Unit 10 failureBlink 10 times, stop 3 sec

For all units Green LED light

Cool ModeGreen LED light On
Indoor coil sensor 2 failureBlink 2 times, stop 3 sec
Return air sensor failureBlink 3 times, stop 3 sec
Indoor coil sensor 1 failureBlink 4 times, stop 3 sec
Indoor coil low temperature protectionBlink 5 times, stop 3 sec
Indoor coil over heat protectionBlink 6 times, stop 3 sec
Water pump failureBlink 7 times, stop 3 sec

For all units Yellow LED light

On/Off timer setLED light On
No On/Off timerLED light Off
Sakura Hydronic Cassette AC Troubleshooting
Sakura Hydronic Cassette AC Troubleshooting

3-Rooftop Package Air Conditioner

When Error, Display will be show as below.

Error CodeMeaning
E1Freeze protection
E2Defrost protection
E3Compressor overload protection
E4Anti overheat protection
E5Low ambient protection
E6Cooling fail
E7Heating fail
E8Sensor error

Hydronic Cassette SFP – KM – DLY Series, Technical-Installation Manual PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

LG VRF Error Codes – Multi V

  Error Codes; Indicate different types of unit failures, assist in self-diagnosis and to track the frequency of occurrence. Error codes are shown on the LED of indoor units, wired remote controller, the outdoor unit control board, and on the main screen of the LG Monitoring View (LGMV) Diagnostic Software. If two or more errors occur simultaneously, the lower error code number is displayed first. After error is resolved, the error code does not display. Error Display; The first, second, and third number on the LED indicates error number; the fourth number on LED indicates outdoor unit number. Examples: 211 = Error No. 21 on master unit, 213 = Error No. 21 on slave2 unit, Error No. 105 on master unit on compressor 1. Error Code Nomenclature Definitions; MICOM: Non-volatile memory chip where unit setup information is stored. EPROM: Non-volatile memory chip where device identification, size, and factory defined default component operating parameters are stored.   LG Multi V Erro...