Innovair Air Conditioner Error Codes

 innovair prestige inverter mini split system:

Innovair Air Conditioner Error Codes
Innovair Air Conditioner Error Codes
Error CodesProblem
E2Anti-freezing protection
E3Block or Low pressure of refrigerant system
E4Compressor exhaust high temperature protection
E5AC over-current protection
E6Communication failure between indoor unit and outdoor unit
E8Anti-high temperature protection
H4Anti-high temperature protection
H6No feedback of indoor fan motor
C5Jumper cap malfunction protection
LPIndoor unit and outdoor unit doesn't match
L3Outdoor DC fan motor malfunction
L9Power protection
FoGathering refrigerant
F1Indoor ambient sensor open or short circuit
F2Indoor tube sensor open or short circuit
F3Outdoor ambient sensor open or short circuit
F4Outdoor tube sensor open or short circuit
F5Exhaust sensor open or short circuit
F6Overload limit / drop frequency
F8Over current limit / drop frequency
F9High exhaust temperature limit / drop frequency
F0Refrigerant leakage protection
FH
Anti-freezing limit / drop frequency
H1Defrosting
H3Compressor overload protection
H5IPM protection
H5Module temperature is too high
HCPFC protection
EELoading EEPROM malfunction
PH
High PN voltage protection
PLLow PN voltage protection
U74-way valve reversal abnormal
d1/d2/d3DRED1 / DRED2 / DRED3
P0Compressor Min frequence in test state
P1Compressor rated frequence in test state
P2Compressor maximum frequence in test state
P3Compressor intermediate frequence in test state
EUFrequency limiting (module temperature )
LUFrequency limiting (power)
JFMalfunction of detecting plate (WIFI )
F0Insufficient fluorine protection

innovair nature inverter mini split system:

Innovair Mini Split AC Error Codes
Innovair Mini Split AC Error Codes
Error CodesProblem
E0Indoor unit EEPROM parameter error
E1Indoor / outdoor units communication error
E2Zero-crossing signal detection error
E3Indoor fan speed has been out of control
E4Indoor room temperature sensor T1 open circuit or short circuit
E5Evaporator coil temperature sensor T2 open circuit or short circuit
ECRefrigerant leakage detection
F1Outdoor temperature sensor T4 open circuit or short circuit
F2Condenser coil temperature sensor T3 open circuit or short circuit
F3Compressor discharge temperature sensor T5 open circuit or short circuit
F4Outdoor unit EEPROM parameter error
P0IPM malfunction or IGBT over-strong current protection
P1Over voltage or over low voltage protection
P4Inverter compressor drive error

Diagnosis and Solution – How to Fix?

Error Code: E0/F4

EEPROM parameter error diagnosis and solution (E0/F4)

Malfunction decision conditions: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.

Supposed causes: Installation mistake, PCB faulty.

Error Code: E1

Indoor / outdoor unit’s communication diagnosis and solution (E1)

Malfunction decision conditions: Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition happens four times continuously.

Supposed causes: Wiring mistake, Indoor or outdoor PCB faulty.

Error Code: E2

Zero crossing detection error diagnosis and solution (E2)

Malfunction decision conditions: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal.

Supposed causes: Connection mistake, PCB faulty.

Error Code: E3

Fan speed has been out of control diagnosis and solution (E3)

Malfunction decision conditions: When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure.

Supposed causes: Wiring mistake, Fan ass’y faulty, Fan motor faulty, PCB faulty.

Error Code: E5

Open circuit or short circuit of temperature sensor diagnosis and solution (E5)

Malfunction decision conditions: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.

Supposed causes: Wiring mistake, Sensor faulty.

Error Code: EC

Refrigerant Leakage Detection diagnosis and solution (EC)

Malfunction decision conditions: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 <Tcool-2℃ does not keep continuous 4 seconds and this situation happens 3 times, the display area will show “EC” and AC will turn off.

Supposed causes: T2 sensor faulty, Indoor PCB faulty, System problems, such as leakage or blocking.

Error Code: P0

IPM malfunction or IGBT over-strong current protection diagnosis and solution (P0)

Malfunction decision conditions: When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show “P0” and AC will turn off.

Supposed causes: Wiring mistake; IPM malfunction; Outdoor fan ass’y faulty Compressor malfunction; Outdoor PCB faulty.

Error Code: P1

Over voltage or too low voltage protection diagnosis and solution (P1)

Malfunction decision conditions: An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.

Supposed causes: Power supply problems, System leakage or block, PCB faulty.

Error Code: P2

High temperature protection of compressor top diagnosis and solution (P2)

Malfunction decision conditions: If the sampling voltage is not 5V, the LED will display the failure.

Supposed causes: Power supply problems, System leakage or block, PCB faulty.

Error Code: P4

Inverter compressor drive error diagnosis and solution (P4)

Malfunction decision conditions: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.

Supposed causes: Wiring mistake; IPM malfunction; Outdoor fan ass’y faulty Compressor malfunction; Outdoor PCB faulty.

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condenser Op

York Chiller Error Codes and Troubleshooting

  Real Time Error Numbers York Chiller Error Codes and Troubleshooting Error Description 0 All Ok 1 Datum Type Ok Test Failed 2 English Text Too Long 3 Floating Point Exception 4 Get Packet Failed 5 Get Type Failed 6 Invalid Unit Conversion 7 Invalid Hardware Selection 8 Real Time Fault 9 Spanish Text Too Long 10 Thread Exited 11 Thread Failed 12 Thread Stalled 13 Io Board Reset 14 Bram Invalid 15 Bacnet Setup Failed Problem:  No display on panel – unit will not start Possible Cause: Main supply to control system OFF. Emergency stop device off. CB3 tripped. No supply to – T2 No 24VAC supply to power board. No +12V output from powerboard. Action: Switch on main supply if safe to do so. Check if control panel emergency stop switch and any remote emergency stop devices are in the OFF position. Turn to ON position (1) if safe to do so. Check CB3 Check 115VAC to L & 2. Check wiring from – T2 to powerboard and fuse. Replace powerboard or isolate excessive load on the board. Problem:  NO

York VRF Error Codes

  Malfunction and Protection Code Table. The display board in digital scroll system is just to display running conditions and  malfunction information. The manual button is just to check the address code and power code  of indoor units. York VRF Error Codes Malfunction and Protection Code Table: Error Codes Contents E0 Phase sequence or lack of phase E1 Communication malfunction E2 T1 sensor malfunction E3 T2A sensor malfunction E4 T2B sensor malfunction E5 T3 sensor malfunction E6 Over-zero checking malfunction E7 EEPROM malfunction E8 Fan motor checking out of control E9 Communication malfunction between PCB and Display board EF Other malfunction EE Water level checking malfunction ED Outdoor protection EC Clear malfunction EB Inverter Module Protection EA Compressor Over-current (4 times) P0 Evaporator Temp. Protection P1 Anti-cooling or Defrost Protection P2 Condenser High Temp. Protection P3 Compressor Temp. Protection P4 Discharge Pipe Temp. Protection P5 Discharge High-pressure