Skip to main content

MRCOOL Air Conditioner Error Codes

 

MRCOOL Air Conditioner Error Codes
MRCOOL Air Conditioner Error Codes

Overview: Fault Display on the Dual 8 Numeral Tube of Outdoor Mainboard

Error CodesMeaning
E1Actuation of high pressure switch
E3Actuation of low pressure switch
E4Air discharge high temperature protection of compressor
F2Malfunction of condenser temperature thermistor
F3Malfunction of outdoor ambient temperature thermistor
F4Malfunction of Exhaust Temp. Sensor
oNNormal operation
H1Defrost operation

How to Fix?

Error Code: E1

Trouble Case: Actuation of high pressure switch

Origin of Trouble Signal: High pressure switch

Measure: Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

Error Code: E3

Trouble Case: Actuation of low pressure switch

Origin of Trouble Signal: Low pressure switch

Measure: When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than 3sec and the system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

Error Code: E4

Trouble Case: Air discharge high temperature protection of compressor

Origin of Trouble Signal: Exhaust over temperature protection

Measure: The exhaust temperature is higher than 125°C for more than 5sec, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90°C for more than 5 sec, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

Error Code: F2

Trouble Case: Malfunction of condenser temperature thermistor

Origin of Trouble Signal: Condenser temperature thermistor

Measure: Malfunction of condenser temperature thermistor is detected when there is a short circuit or an open circuit in the condenser temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

Error Code: F3

Trouble Case: Malfunction of outdoor ambient temperature thermistor

Origin of Trouble Signal: Outdoor ambient temperature thermistor

Measure: Malfunction outdoor ambient temperature thermistor is detected when there is a short circuit or an open circuit in the outdoor ambient temperature thermistor for more than 5 sec. The system will be shut down. The reset for the malfunction of condenser temperature thermistor is automatic.

Error Code: F4

Trouble Case: Malfunction of Exhaust Temp. Sensor

Origin of Trouble Signal: Exhaust temperature sensor

Measure: If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 2 minutes or short circuit 5 seconds successively at any time .The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

Error Code: oN

Trouble Case: Normal operation

Origin of Trouble Signal: Unit operating normally or in standby mode.

Error Code: H1

Trouble Case: Defrost operation

Origin of Trouble Signal: Unit operating in defrost

Error Analysis

Trouble Case: Power problem

Measure:

  1. Check control transformer power (24V).
  2. If power is available to demand control board and LED(s) do not light, replace control board.

Trouble Case: Actuation of high pressure switch

Measure: Abnormality is detected when the contact of the high pressure switch opens for 3 sec. The system will be shut down. The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

Trouble Case: Actuation of low pressure switch

Measure: When the unit runs more than 4 minutes or does not run, the low pressure switch opens for more than3sec and the system will be shut down..The unit will report this fault. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

Trouble Case: Air discharge high- temperature protection of compressor

Measure: The exhaust temperature is higher than 125°C for more than 5s, the system will be shut down. After stopping the compressor for 3 mins, if the exhaust temperature is lower than 90°C for more than 5s, the compressor will re-start. For the first two faults within 30 minutes, the unit can be recovered automatically. If over three times, the unit cannot be recovered automatically.

Trouble Case: Malfunction of exhaust Temp. Sensor

Measure: If the exhaust temperature sensor is detected of open circuit 5 seconds successively after the compressor is started for 3 minutes or short circuit 5 seconds successively at any time The system will be shut down. After the fault is eliminated, the system can automatically resume to operation.

For 13 SEER R410A Unitary Ducted Split AC & Heat Pump

Olympus Series Mid-Static Duct Air Handler

Fault CodesSolutions
E0Indoor EEPROM error
E1Communication malfunction between indoor and outdoor units
E3Indoor fan speed malfunction
E4Indoor room temperature sensor open circuit or short circuit
E5Evaporator coil temperature sensor open circuit or short circuit
ECRefrigerant leakage detection malfunction
EEWater-level alarm malfunction
E8Communication malfunction between two indoor units (for twins model)
E9Other malfunction of twins model
F0Current overload protection
F1Outdoor room temperature sensor open circuit or short circuit
F2Outdoor condenser pipe temperature sensor error
F3Discharging air temperature sensor error
F4Outdoor EEPROM error
F5Outdoor fan speed malfunction (Only for DC fan motor)
F6T2b sensor error
P0Inverter module IPM protection
P1High/Low voltage protection
P2High temperature protection of compressor top
P3Outdoor low temp. protection
P4Compressor drive error
P5Mode conflict

MRCOOL Split AC Manual PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

York Chiller Error Codes and Troubleshooting

  Real Time Error Numbers York Chiller Error Codes and Troubleshooting Error Description 0 All Ok 1 Datum Type Ok Test Failed 2 English Text Too Long 3 Floating Point Exception 4 Get Packet Failed 5 Get Type Failed 6 Invalid Unit Conversion 7 Invalid Hardware Selection 8 Real Time Fault 9 Spanish Text Too Long 10 Thread Exited 11 Thread Failed 12 Thread Stalled 13 Io Board Reset 14 Bram Invalid 15 Bacnet Setup Failed Problem:  No display on panel – unit will not start Possible Cause: Main supply to control system OFF. Emergency stop device off. CB3 tripped. No supply to – T2 No 24VAC supply to power board. No +12V output from powerboard. Action: Switch on main supply if safe to do so. Check if control panel emergency stop switch and any remote emergency stop devices are in the OFF position. Turn to ON position (1) if safe to do so. Check CB3 Check 115VAC to L & 2. Check wiring from – T2 to powerboard and fuse. Replace powerboard or isolate excessive loa...