Midea Chiller Error Codes

 Midea Package Air-cooled Modular Chiller Error Codes

Midea Chiller Error Codes
Midea Chiller Error Codes

Code Trouble:

Error CodesCause
E0Water-flow detection error (the third time)
E1Power phases sequence failure
E2Communication failure
E3Total outlet water Temperature sensor failure (available for main unit)
E4Outlet water temperature sensor in double-pipe heat interchanger error
E5Pipe temperature sensor in condenser A error
E6Pipe temperature sensor in condenser B error
E7Outdoor Temperature sensor failure
E8Error of the Air Exhaust Temp. Sensor at Digital Compressor
E9Water-flow check trouble(wire controller and control board can recover automatically when the trouble is displayed for the first and second times
EAMain unit detect that auxiliary unit’s quantity have decreased.
EbFreeze-proof temperature sensor 1 in double-pipe heat interchanger error
ECWire controller can not search the modules on line
EDWire control and module unit communication error
Ed1-hour consecutive 4-times PE protection
EEWire control and computer communication error
EFInlet water temperature sensor error
P0System A high-pressure protection or discharge gas temperature protection
P1System A low-pressure protection
P2System B high-pressure protection or discharge gas temperature protection
P3System B low-pressure protection
P4System A current protection
P5System B current protection
P6System A Condenser high-temperature protection
P7System B Condenser high-Temperature protection
P8Digital compressor discharge Temperature protection, when it is above 125℃
PbSystem anti-freeze protection
PELow-temperature protection of double-pipe heat interchanger
F1Eeprom failure
F2Failure of reduction of wired controller number at parallel connection of multiple wired controller (reserved)
CPAnti-freeze protection of plate heat exchanger for 5/7kW
CLProtection when temperature difference between inlet & outlet water in cooling mode is too large for 5/7kW.
CHProtection when temperature difference between inlet & outlet water in heating mode is too large for 5/7kW
C8Water flow switch protection malfunction
C0Temperature sensor malfunction of plate heat exchanger for 5/7kW.
d8Remote control
HHInlet water temperature sensor malfunction for 5/7kW models.
Midea Chiller Remote Control
Midea Chiller Remote Control

Troubleshooting and Solutions

Troubles: Over high air discharge pressure(Cooling operation).

Possible reasons:

  1. Air or other non-condensing gas still in the system.
  2. Fins in the condenser are dirty or foreign substance blocking fins.
  3. Insufficient chilling air volume or condenser fan error.
  4. Excessive high air suction pressure.
  5. Excessive refrigerant charging volume.
  6. Over high ambient temperature.

Solutions:

  1. Discharge gas from refrigerant charging inlet. Re-vacuum the system if necessary.
  2. Clean condenser fins.
  3. Check and repair the condenser fan, recover the normal operation.
  4. See “Excessive high air suction pressure”.
  5. Discharge the excessive refrigerant.
  6. Check ambient temperature.

Troubles: Over low air discharge pressure (Cooling operation).

Possible reasons:

  1. Surrounding temperature is lower.
  2. Refrigerant leak or insufficient.
  3. Low suction pressure.

Solutions:

  1. Measure the surrounding temp.
  2. Leak-hunting or recharging.
  3. Refer to the “low suction pressure”.

Troubles: Over high air suction pressure (Cooling operation).

Possible reasons:

  1. Refrigerant over-charged.
  2. High temperature of the inlet chilled-water.

Solutions:

  1. Discharge the additional refrigerant.
  2. Check the heat insulation of water pipeline.

Troubles: Compressor stops because of freeze-proof protection

Possible reasons:

  1. Insufficient chilling water flow volume.
  2. Gas still in water loop.
  3. Thermal resistor error.

Solutions:

  1. Error comes from pump or flow-type water volume control. Check and repaired or replace a new one.
  2. Discharge air.
  3. Upon error have been confirmed, please replace a new one.

Troubles: Compressor can‟t start.

Possible reasons:

  1. Over current relay trip up, fuse burnt out.
  2. Control circuit without power though.
  3. High voltage or low voltage protection.
  4. Coils in contactor are burnt out.
  5. Wrong connection of phase sequence.
  6. Water system error and flow type volume controller short connection.
  7. Error signal delivered from wired controller.

Solutions:

  1. Replace damaged assembly.
  2. Check the wring of control system.
  3. Reference to mention in above the parts of air suction and discharge pressure error.
  4. Replace damaged assembly.
  5. Re-connect and adjust the any 2 wires among 3 phases.
  6. Check water system.
  7. Find out the error type and carry out the corresponding measure to settle.
Midea Chiller Parts
Midea Chiller Parts
Connection Method
Connection Method
65kW module refrigeration system sketch drawing(Fixed speed)
65kW module refrigeration system sketch drawing(Fixed speed)


Midea Chiller Service Manual PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

LG VRF Error Codes – Multi V

  Error Codes; Indicate different types of unit failures, assist in self-diagnosis and to track the frequency of occurrence. Error codes are shown on the LED of indoor units, wired remote controller, the outdoor unit control board, and on the main screen of the LG Monitoring View (LGMV) Diagnostic Software. If two or more errors occur simultaneously, the lower error code number is displayed first. After error is resolved, the error code does not display. Error Display; The first, second, and third number on the LED indicates error number; the fourth number on LED indicates outdoor unit number. Examples: 211 = Error No. 21 on master unit, 213 = Error No. 21 on slave2 unit, Error No. 105 on master unit on compressor 1. Error Code Nomenclature Definitions; MICOM: Non-volatile memory chip where unit setup information is stored. EPROM: Non-volatile memory chip where device identification, size, and factory defined default component operating parameters are stored.   LG Multi V Erro...

Innovair Air Conditioner Error Codes

 innovair  prestige  inverter mini split system: Innovair Air Conditioner Error Codes Error Codes Problem E2 Anti-freezing protection E3 Block or Low pressure of refrigerant system E4 Compressor exhaust high temperature protection E5 AC over-current protection E6 Communication failure between indoor unit and outdoor unit E8 Anti-high temperature protection H4 Anti-high temperature protection H6 No feedback of indoor fan motor C5 Jumper cap malfunction protection LP Indoor unit and outdoor unit doesn't match L3 Outdoor DC fan motor malfunction L9 Power protection Fo Gathering refrigerant F1 Indoor ambient sensor open or short circuit F2 Indoor tube sensor open or short circuit F3 Outdoor ambient sensor open or short circuit F4 Outdoor tube sensor open or short circuit F5 Exhaust sensor open or short circuit F6 Overload limit / drop frequency F8 Over current limit / drop frequency F9 High exhaust temperature limit / drop frequency F0 Refrigerant leakage protection FH Anti-f...