Haier MRV Air Conditioner Error Codes

 Haier Commercial Air Conditioning, Fault Code List for H-MRV Indoor Unit

Haier MRV Air Conditioner Error Codes
Haier MRV Air Conditioner Error Codes
Models with wired controllerFault description-Models with remote controller
E3Fault in liquid pipe temp. sensor. 1 flash of Timer indicator
E4Fault in suction pipe temp. sensor. 2 flashes of Timer indicator
E9Communication error between indoor and outdoor units. 4 flashes of Timer indicator
E7Communication error between indoor unit and PCB of PMV valve. 5 flashes of Timer indicator
E5Communication error between 846 and 808 chips. 6 flashes of Timer indicator
E0Fault in float switch or pump motor. 11 flashes of Timer indicator
E1Fault in outdoor unit
E8Communication error between wired controller and indoor unit PCB

AU482FIBHA Fault Code List

Digital readoutDescription
01The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. The fault is fixable
02The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. The fault is fixable
03The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. The fault is fixable.
04After 3 minutes of compressor operation, the detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. Fixable when below 80°C.
05The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds.
06An alarm is given five seconds after the current limit is exceeded. Where there are 3 alarms within 30 minutes, the fault code is displayed. The fault is not fixable
07When the compressor is shut off, the detected current of current sensor is above 15A, and when the compressor is started, the operating frequency is above 60Hz and the detected current is below 5A. The fault is fixable.
08The overload protector of inverter compressor is activated.
09IPM overcurrent, short-circuit, overtemperature and undervoltage. When the fault occurs three times within 30 minutes, an alarm is given and the fault is not fixable.
10857 EEPROM data access error, 11 flashes. The fault is not fixable.
11When the compressor is started, the temperature detected by TD1 sensor is above 120°C. The compressor is shut off in 5 seconds and an alarm is given. Where there are 3 alarms within 30 minutes, the fault code 11 is displayed. The fault is not fixable.
13Pressure switch is activated. The fault is corrected after the normal pressure is restored for 2 minutes.
16After the compressor has operated for 10 minutes, the temperature detected by TS sensor is above 40°C. Corrected in 2 minutes.
19When the inverter compressor operates at a frequency of S3 and S4, the temperature detected by TD1 sensor is above 110°C.
20200 times of failure in transmission. An alarm is given and the indicator flashes.
21200 times of failure in transmission. The fault code is displayed.
22Receiving no signals from indoor unit for 4 minutes. The fault code 22 is displayed.
23An alarm is given and the fault code is displayed.

Note: The model is provided with 1 high-pressure switch and 1 low-pressure switch in series. The compressor features a built-in compressor overload protector.

AU242FHBHA Fault Code List

Number of flashes by fault indicatorDescription
1The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. The fault is fixable.
2The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. The fault is fixable.
3The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. The fault is fixable.
4After 3 minutes of compressor operation, the detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds. Fixable when below 80°C.
5The detected sensor value is below 20H (open-circuit) or above 1000H (short-circuit) for 60 seconds.
6An alarm is given five seconds after the current limit is exceeded. Where there are 3 alarms within 30 minutes, the fault code is displayed. The fault is not fixable.
9IPM overcurrent, short-circuit, overtemperature and undervoltage. When the fault occurs three times within 30 minutes, an alarm is given and the fault is not fixable.
10857 EEPROM data access error, 11 flashes. The fault is not fixable.
11After the compressor is started, the temperature detected by TD1 sensor is above 120°C. The compressor is shut off in 5 seconds and an alarm is given. Where there are 3 alarms within 30 minutes, the fault code 11 is displayed. The fault is not fixable.
12857-to-809 transmission error
13The high pressure switch is activated. The fault is corrected after the normal pressure is restored for 2 minutes.
Haier MRV Air Conditioner Fault Codes
Haier MRV Air Conditioner Fault Codes

Haier MRV S Fault Code List

Digital tube indication on master unitFailure code definition
20Defrosting temp. sensor TE1 failure
20-1Defrosting temp. sensor TE2 failure
21Ambient temp. sensor Ta failure
22Suction temp. sensor Ts failure
23Discharging temp. sensor Td failure
24Oil temp. sensor Toil failure
26-0Indoor communication failureI
26-1Indoor communication failureI
26-2Indoor communication failureI
27Oil temp.too high protection (Toil)
28High pressure sensor Pd failure
29-1DLow pressure sensor Ps failure
30High pressure switch HPSi failure
33EEPROM failure
34Discharging temp. too high protection (Td)
354-way valve reversing failure
36Oil temp. too low protection (Toil)
39-0Low pressure sensor Ps too low protection
39-1Compression ratio too high protection
39-2Compression ratio too low protection
40High pressure sensor Pd too high protection
43Discharging temp. sensor Td too low protection
46Communication with inverter board failure
71DC motor blocked
75No pressure drop between high pressure and low one
78Lack of refrigerant
110IPM modular protection (F0)
111Compressor out of control
112Radiator of transducer temp.too high
113Transducer overload
114Voltage too low of DC bus line of transducer
115Voltage too high of DC bus line of transducer
116Communication abnormal between transducer and control PCB
117Transducer over current (software)
118Compressor startup failure
120Power supply of transducer abnormal
121Power supply of inverter board is abnormal
122Radiator temp. sensor of transducer abnormal

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

LG VRF Error Codes – Multi V

  Error Codes; Indicate different types of unit failures, assist in self-diagnosis and to track the frequency of occurrence. Error codes are shown on the LED of indoor units, wired remote controller, the outdoor unit control board, and on the main screen of the LG Monitoring View (LGMV) Diagnostic Software. If two or more errors occur simultaneously, the lower error code number is displayed first. After error is resolved, the error code does not display. Error Display; The first, second, and third number on the LED indicates error number; the fourth number on LED indicates outdoor unit number. Examples: 211 = Error No. 21 on master unit, 213 = Error No. 21 on slave2 unit, Error No. 105 on master unit on compressor 1. Error Code Nomenclature Definitions; MICOM: Non-volatile memory chip where unit setup information is stored. EPROM: Non-volatile memory chip where device identification, size, and factory defined default component operating parameters are stored.   LG Multi V Erro...