Skip to main content

Gree Multi Inverter VRF Error Codes

 The repair personnel shall collect the error information as more as possible for careful study and list those electric or system parts that might cause the error. Then, the repair personnel shall be able to identify the specific cause of error and find out the problem parts.

Gree Multi Inverter VRF Error Codes
Gree Multi Inverter VRF Error Codes

List of Unit Errors-List of Error Display on Wired Controller:

Error CodesSolution
E1Compressorhigh-pressureprotection. The high pressure protection value is 4.2MPa. When it is detected three times successively that a compressor is under high pressure, this compressor will be stopped. In this case, error code E1 will be displayed and the run indicator will blink.
E2Indoor antifreeze protection. When it is detected for 10 minutes successively that Tevap. is ≤-2℃ (varying with indoor unit), the antifreeze protection will be activated, in which case the outdoor unit will immediately shut off the indoor electronic expansion valve and the capacity will be set to “0”.
E3Compressor low-pressure protection. When the low pressure reaches the protection value (absolute pressure: 0.15MPa), the low pressure switch will be cut off, in which case the low pressure protection will be displayed.
E4Compressor exhaust temperature protection. When the exhaust temperature (Texhau.) is equal to and higher than 113℃, the compressor will be stopped. Upon the first occurrence of exhaust protection, the error code E4 will be displayed. When the exhaust temperature is lower than TR℃, the compressor will resume to operation after it has been stopped for 3 minutes. The compressor can resume to operation for the first two times. But if this occurs three times successively in 1 hour, the unit must be disconnected from power supply before it can restarted
E5Frequency converter over current protection. The drive board of variable frequency compressor is incurred to error. For details on the error message, please refer to the Display Code on Digital Tube of Outdoor Unit.
E6Communication error. The mainboard of indoor unit or the wired control is incurred to communication error with outdoor unit. The indoor unit incurred to communication error will be stopped and display the error code.
E7Mode conflict. The run mode of the unit that is started later is inconsistent to the mode that is started earlier. Only the cooling and dry mode has possible mode conflict against the heat mode. For fan mode, there is no mode conflict against the cooling, dry or heat mode. In case mode conflict occurs, the indoor unit with mode conflict will display E7 and be stopped.
E9Water-full protection. When water full is detected for 8 seconds successively, the system will enter into water-full protection state, in which case the wired controller will display E9 and give out alarm. In case of water-full protection under each mode, the other loads of the indoor unit will be stopped, except that the water pump will remain working and give out alarm. In this case, the outdoor unit shall adjust the capacity output accordingly.
F0Indoor ambient temperature sensor error. The indoor unit incurred to sensor error will display error code and be stopped.
F1Indoor coil inlet temperature sensor error. The indoor unit incurred to sensor error will display error code and be stopped.
F2Indoor coil middle temperature sensor error. The indoor unit incurred to sensor error will display error code and be stopped.
F3Outdoor coil inlet temperature sensor error. The indoor unit incurred to sensor error will display error code and be stopped.
F4Outdoor ambient temperature sensor error. Test for 30 seconds successively to check if the temperature sensor is disconnected. If yes, alarm will be sent; otherwise no processing will be made. If the controller of outdoor unit detects failure of outdoor sensor under open circuit, short circuit and excess of test value, the outdoor unit will execute the following default actions, that is, the error message will be sent to each indoor unit and the error code will be displayed via error indicator or wired controller. When the outdoor ambient temperature is lower than -5℃, the disconnection failure of outdoor inlet, middle and exit sensors in shield room will be processed as under -30℃.
F7Outdoor defrost temperature sensor error. Test for 30 seconds successively to check if the temperature sensor is disconnected. If yes, alarm will be sent; otherwise no processing will be made. If the controller of outdoor unit detects failure of outdoor sensor under open circuit, short circuit and excess of test value, the outdoor unit will execute the following default actions, that is, the error message will be sent to each indoor unit and the error code will be displayed via error indicator or wired controller. When the outdoor ambient temperature is lower than -5℃, the disconnection failure of outdoor inlet, middle and exit sensors in shield room will be processed as under -30℃.
F9
Exhaust temperature sensor error. Test for 30 seconds successively to check if the temperature sensor is disconnected. If yes, alarm will be sent; otherwise no processing will be made. If the controller of outdoor unit detects failure of outdoor sensor under open circuit, short circuit and excess of test value, the outdoor unit will execute the following default actions, that is, the error message will be sent to each indoor unit and the error code will be displayed via error indicator or wired controller. When the outdoor ambient temperature is lower than -5℃, the disconnection failure of outdoor inlet, middle and exit sensors in shield room will be processed as under -30℃.

Trouble Display of Indoor Unit

  • E1: High-pressure protection
  • E2: Prevention against low temperature
  • E3: Low-pressure protection
  • E4: Exhaust overtemperature
  • E5: Overcurrent Protector
  • E6: Communication error
  • E9: Water-full protection
  • F0: Indoor ambient temperature sensor error
  • F1: Indoor tube-inlet sensor error
  • F2: Indoor tube-middle sensor error
  • F3: Indoor tube-exit sensor error
  • F4: Outdoor ambient temperature sensor error
  • F5: Outdoor tube-inlet sensor error
  • F6: Outdoor tube-middle sensor error
  • F7: Outdoor tube-exit sensor error
  • F8: Error with exhaust temperature sensor 1 (fixed-frequency)
  • F9: Error with exhaust temperature sensor 2 (digital)
  • FA: Error with oil temperature sensor 1 (fixed-frequency)
  • Fb: Error with oil temperature sensor 2 (digital)
  • Fc: High-pressure valve error
  • Fd: Low-pressure valve error
  • EH: Thermal relay error

Warning mark code:

  • HO: Main wire controller mark
  • SL: Slave wire controller mark
  • CH: Mark of confilcting with the effective main wire controller
  • CL: Mark of eliminating main wire
  • No: No main indoor unit
  • CC: Romote shield
  • EE: Key locked

Modular D.C. Inverter Multi VRF Error Codes

Trouble display of mainboard LED of duct type indoor unit

  • F4: Outdoor ambient temperature sensor error
  • F5: Outdoor tube-inlet sensor error
  • F6: Outdoor tube-middle sensor error
  • F7: Outdoor tube-exit sensor error
  • F8: Error with exhaust temperature sensor 1 (fixed-frequency)
  • F1: Indoor tube-inlet sensor error
  • F2: Indoor tube-middle sensor error
  • F3: Indoor tube-exit sensor error
  • F9: Error with exhaust temperature sensor 2 (digital)
  • FA: Error with oil temperature sensor 1 (fixed-frequency)
  • Fb: Error with oil temperature sensor 2 (digital)
  • F0: Indoor ambient temperature sensor error
  • E4: Exhaust overtemperature
  • E3: Low-pressure protection
  • E5: Overcurrent Protector
  • E1: High-pressure protection
  • E6: Communication error
  • Fc: High-pressure valve error
  • Fd: Low-pressure valve error
  • Eb: Water-full protection (Cassette)
Trouble display of mainboard LED of cassette type indoor unit
Trouble display of mainboard LED of cassette type indoor unit

 

Trouble display of mainboard LED of floor ceiling type
Trouble display of mainboard LED of floor ceiling type
E2-F4-F5-F6-F7-F8-F1-F2-F3-F9-FA-FB-F0-E4-E3-E5-E1-E6-FC-FD-EB
E2-F4-F5-F6-F7-F8-F1-F2-F3-F9-FA-FB-F0-E4-E3-E5-E1-E6-FC-FD-EB
Number of indoor units display
Number of indoor units display

Common Troubleshooting

Check the following items before contacting for repair.

Phenomenon: The unit doesn’t run.

Reason-Measure:

  • Without power supply. Connect to power supply.
  • Voltage is too low. Check if the voltage is within rating range.
  • Broken fuse or breaker trips off. Replace fuse or connect breaker.
  • Insufficient energy of remote controller. Replace new battery.
  • Remote controller is out of control scope. Control scope is within 8m.

Phenomenon: Abnormal cooling or heating

Reason-Measure:

  • Air intake or outlet of indoor or outdoor unit is blocked. Remove obstruction.
  • Improper temperature setting. Adjust setting at wireless remote controller or wired controller.
  • Fan speed is set too low. Adjust setting at wireless remote controller or wired controller.
  • Wind direction is not correct. Adjust setting at wireless remote controller or wired controller.
  • Door or windows are opened. Close the door or windows.
  • Direct sunshine. Draw curtain or louver.
  • Too many heat resources in the room. Reduce heat resources.
  • Filter is blocked for dirt. Clean the filter.

 MODULAR D.C. INVERTER MULTI VRF Service Manual PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

York Chiller Error Codes and Troubleshooting

  Real Time Error Numbers York Chiller Error Codes and Troubleshooting Error Description 0 All Ok 1 Datum Type Ok Test Failed 2 English Text Too Long 3 Floating Point Exception 4 Get Packet Failed 5 Get Type Failed 6 Invalid Unit Conversion 7 Invalid Hardware Selection 8 Real Time Fault 9 Spanish Text Too Long 10 Thread Exited 11 Thread Failed 12 Thread Stalled 13 Io Board Reset 14 Bram Invalid 15 Bacnet Setup Failed Problem:  No display on panel – unit will not start Possible Cause: Main supply to control system OFF. Emergency stop device off. CB3 tripped. No supply to – T2 No 24VAC supply to power board. No +12V output from powerboard. Action: Switch on main supply if safe to do so. Check if control panel emergency stop switch and any remote emergency stop devices are in the OFF position. Turn to ON position (1) if safe to do so. Check CB3 Check 115VAC to L & 2. Check wiring from – T2 to powerboard and fuse. Replace powerboard or isolate excessive loa...