Skip to main content

Dometic Thermostat Error Codes

 When the system determines that one of the faults listed below has occurred an error code will be displayed in the LCD.

Dometic Thermostat Error Codes
Dometic Thermostat Error Codes
Error CodesSolution
E1Loss of communication between the CCC 2 thermostat and all system power module boards. System will shut down.
E1Loss of communication between the CCC 2 thermostat and an individual system power module board. The LED will display error code EI and the zone num- ber that lost communication. Any additional zones that loose communication will blink in addition to the current zone.
E2Open circuit or out-of-range indoor temperature sensor. All heat , cool, and de- humidify operations will be locked out. Manual fan operation will continue.
E3Shorted Indoor Temperature Sensor. All heat, cool, and dehumidify operation will be locked out. Manual fan operation will continue.
E4Open circuit or out of range Outdoor Temperature Sensor (select models). Heat pump and dehumidification operation will be locked out. Air conditioner, furnace, heat strip and fan operation can continue to operate.
E5Open circuit or out of range Freeze Sensor. Air conditioner and dehumidification operation will be locked out. Heat pump, furnace, heat strip and fan operation can continue to operate but displays the last temperature set-point.
E6Open circuit Humidity Sensor (Select Models). Air conditioner and dehumidifica- tion will be locked out. Heat pump, furnace heat strip and fan can continue to operate.
E7Loss of 120 VAC power to all power module boards on the system. The system will shut down.
E8Invalid zone configuration. The heat pump and heat strip DIP switches are both set to the ON position in one zone. Heat pump, heat strip, air conditioner, and dehumidify operation will be locked out in the affected zone.
E9Invalid zone configuration. The dehumidifier DIP switch and either the heat pump or heat strip DIP switches are set to the ON position in one zone. Heat pump, heat strip, air conditioner, and dehumidify operation will be locked out in the af- fected zone.

System Reset Procedure

When your unit was installed the appropriate dip switches on the electronic control board were turned on to match your system configuration. Any time these settings are changed, a system reset will need to be done before the CCC 2 thermostat will recognize the updated selection.

Dometic thermostat error codes-E1-E2-E3-E4-E5-E6-E7-E8-E9
Dometic thermostat error codes-E1-E2-E3-E4-E5-E6-E7-E8-E9

To do a system reset:

  • Make sure the CCC 2 thermostat is in the OFF mode.
  • Simultaneously press the MODE and ZONE buttons. The LCD will display “IniT” and all available zones.
  • Release the MODE and ZONE buttons.
  • Press the ON/OFF button to exit system set up.

Maintenance

Air Filter – Periodic cleaning or replacement of the air conditioner/heat pump air filters is required. When a system fan run time exceeds 1000 hours the filter icon is displayed in the LCD. See “Quick reference to LCD icons” on page 3. When this occurs wash the filter with soap and warm water. Let dry and reinstall. NEVER run the air conditioner without the air filter in place. This may plug the unit evaporator coil with dirt and substantially degrade the performance of the unit. To reset the fan run time and clear the filter icon, hold the INSIDE and OUTSIDE but- tons for three seconds. This will clear the fan run time for the current zone selected. Dometic CCC 2 thermostat: Clean the CCC 2 thermostat with a moist soft cloth. DO NOT spray water directly on the CCC 2 thermostat. DO NOT use solvents for cleaning.

Service

In the unlikely event the unit fails to operate or operates improperly, check the following before calling your service center.

  1. If your RV is connected to a motor generator, check to be sure the motor genera- tor is running and producing power.
  2. If the RV is connected to a power supply by a land line, check to be sure the line is sized properly to run air conditioner load and it is plugged into the power supply.
  3. Check your 120 VAC fuse or circuit breaker to see if it is open. Insure fuse is not burnt, or circuit breaker is ”ON” and not activated.
  4. Check your 12 VDC fuse or circuit breaker to see if it is open.
  5. After the above checks, call your local service center for further help. This unit must be serviced by qualified service personnel only.
Dometic Thermostat- Quick reference to LCD icons
Dometic Thermostat- Quick reference to LCD icons

When calling for service, always give the following:

  1. Unit Model Number and Serial Number found on Identification Label located on the Base Pan of unit bottom. It is necessary to remove the return air cover to expose the rating plate.
  2. Electronic Control Kit Part Number and Serial Number found on Identification Label located on the side of the Kit. This kit is mounted in the return air cavity and can be exposed by removing the return air cover.

Dometic Thermostat MANUAL PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condenser Op

York Chiller Error Codes and Troubleshooting

  Real Time Error Numbers York Chiller Error Codes and Troubleshooting Error Description 0 All Ok 1 Datum Type Ok Test Failed 2 English Text Too Long 3 Floating Point Exception 4 Get Packet Failed 5 Get Type Failed 6 Invalid Unit Conversion 7 Invalid Hardware Selection 8 Real Time Fault 9 Spanish Text Too Long 10 Thread Exited 11 Thread Failed 12 Thread Stalled 13 Io Board Reset 14 Bram Invalid 15 Bacnet Setup Failed Problem:  No display on panel – unit will not start Possible Cause: Main supply to control system OFF. Emergency stop device off. CB3 tripped. No supply to – T2 No 24VAC supply to power board. No +12V output from powerboard. Action: Switch on main supply if safe to do so. Check if control panel emergency stop switch and any remote emergency stop devices are in the OFF position. Turn to ON position (1) if safe to do so. Check CB3 Check 115VAC to L & 2. Check wiring from – T2 to powerboard and fuse. Replace powerboard or isolate excessive load on the board. Problem:  NO

York VRF Error Codes

  Malfunction and Protection Code Table. The display board in digital scroll system is just to display running conditions and  malfunction information. The manual button is just to check the address code and power code  of indoor units. York VRF Error Codes Malfunction and Protection Code Table: Error Codes Contents E0 Phase sequence or lack of phase E1 Communication malfunction E2 T1 sensor malfunction E3 T2A sensor malfunction E4 T2B sensor malfunction E5 T3 sensor malfunction E6 Over-zero checking malfunction E7 EEPROM malfunction E8 Fan motor checking out of control E9 Communication malfunction between PCB and Display board EF Other malfunction EE Water level checking malfunction ED Outdoor protection EC Clear malfunction EB Inverter Module Protection EA Compressor Over-current (4 times) P0 Evaporator Temp. Protection P1 Anti-cooling or Defrost Protection P2 Condenser High Temp. Protection P3 Compressor Temp. Protection P4 Discharge Pipe Temp. Protection P5 Discharge High-pressure