Skip to main content

Carrier Cassette Air Conditioner Error Codes

 Carrier cassette fault codes; Once a failure occurs with the indoor unit in operation, the green unit LED flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 5 seconds elapses.

Carrier Cassette Air Conditioner Fault Codes
Carrier Cassette Air Conditioner Fault Codes

Carrier Fault Codes and Troubleshooting

Once a failure occurs with the indoor unit in operation, the green unit LED flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 5 seconds elapses.

Error CodesDescription
3Room air sensor fault
2Condensate discharge pump
4Indoor unit coil sensor fault
6Filter dirty
7Outdoor unit failure
10EEPROM corrupt
11Card serial number damaged
12Address / zone incomplete
13Gas flow distributor corrupt
14Outdoor air thermistor
Carrier Cassette Display of Selected Functions
Carrier Cassette Display of Selected Functions

 

Aircon will not start:

  • The main switch is switched OFF, place the switch in the ON position.
  • The fuses on the main switch are burnt out; replace the fuses. ( this operation need to be carried out by qualified personnel only).
  • Wait for 3 minutes: protection against frequent compressor cycling is ON.
  • Selected temperature is higher than the room temperature (or lower in the heating mode).

The unit emits unpleasant smells:

Unpleasant smells can accumulate on the air filters and then be dispersed into the room during air conditioner operation. Switch the unit OFF and contact an authorised service centre to have the filters cleaned. Restart unit in the ventilation (fan only) mode and open windows to change room air.

The unit makes strange noises:

Occasionally the unit makes strange noises at start-up, during operation or when it has stopped. These are generally due to the effect of temperature changes on the plastic parts.

Air conditioner is not supplying enough cooling (or heating):

  • Air cannot circulate freely.
  • Dirty filter reduces air quantity circulating.
  • Filter must be cleaned by skilled personnel only.
  • Doors and/or windows are open.
  • Fan speed has been set to ‘low’.
  • Air flow direction is not correct for optimum ventilation.
  • Selected temperature is not correct.

P (Green LED) indicator is flashing:

System malfunction. Contact service organisation after having ensured that:

  • Air circulation is not obstructed.
  • Outdoor unit coil is not obstructed and causing severe reduction of air circulation.
  • Condensate drainage tube is not obstructed.

As regards fault codes to be communicated to the after-sales

Q (Red LED) indicator is illuminated:

In the heating mode, the LED switches on to indicate an active defrost condition.

Periodical checks

Carrier Cassette Periodical Checks
Carrier Cassette Periodical Checks

Carrier Cassette Air Conditioner  MANUAL PDF

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

Innovair Air Conditioner Error Codes

 innovair  prestige  inverter mini split system: Innovair Air Conditioner Error Codes Error Codes Problem E2 Anti-freezing protection E3 Block or Low pressure of refrigerant system E4 Compressor exhaust high temperature protection E5 AC over-current protection E6 Communication failure between indoor unit and outdoor unit E8 Anti-high temperature protection H4 Anti-high temperature protection H6 No feedback of indoor fan motor C5 Jumper cap malfunction protection LP Indoor unit and outdoor unit doesn't match L3 Outdoor DC fan motor malfunction L9 Power protection Fo Gathering refrigerant F1 Indoor ambient sensor open or short circuit F2 Indoor tube sensor open or short circuit F3 Outdoor ambient sensor open or short circuit F4 Outdoor tube sensor open or short circuit F5 Exhaust sensor open or short circuit F6 Overload limit / drop frequency F8 Over current limit / drop frequency F9 High exhaust temperature limit / drop frequency F0 Refrigerant leakage protection FH Anti-f...