DuctlessAire Air Conditioner Error Codes

 Ductlessair Mini Split AC Error Codes

DuctlessAire Air Conditioner Error Codes
DuctlessAire Air Conditioner Error Codes

Indoor Unit Error Display;

Operation lampTimer lampDisplayLED STATUS
☆ 1 timeXE0Indoor unit EEPROM parameter error
☆ 2 timesXE1Indoor / outdoor units communication error
☆ 3 timesXE2Zero-crossing signal detection error
☆ 4 timesXE3Indoor fan speed has been out of control
☆ 5 timesXE4Indoor room temperature sensor T1 open circuit or short
circuit
☆ 6 timesXE5Evaporator coil temperature sensor T2 open circuit or
short circuit
☆ 7 timesXECRefrigerant leakage detection
☆ 2 timesOF1Outdoor temperature sensor T4 open circuit or short
circuit
☆ 3 timesOF2Condenser coil temperature sensor T3 open circuit or
short circuit
☆ 4 timesOF3Compressor discharge temperature sensor T5 open
circuit or short circuit
☆ 5 timesOF4Outdoor unit EEPROM parameter error
☆ 6 timesOF5Outdoor fan speed has been out of control(only for)
☆ 1 timesP0IPM malfunction or IGBT over-strong current protection
☆ 2 timesP1Over voltage or over low voltage protection
☆ 3 timesP2High temperature protection of compressor top diagnosis
and solution(only for MS11D-21HRDN1-MN5Q1W model)
☆ 5 timesP4Inverter compressor drive error

 

Error Code: P4

Malfunction decision conditions: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.

Error Code: P2

Malfunction decision conditions: If the sampling voltage is not 5V, the LED will display the failure.

Error Code: P1

Malfunction decision conditions: An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.

Error Code: P0

Malfunction decision conditions: When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show “P0” and AC will turn off.

Error Code: EC

Malfunction decision conditions: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.

Error Code: E5

Malfunction decision conditions: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.

Error Code: E3

Malfunction decision conditions: When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure.

Error Code: E2

Malfunction decision conditions: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal.

Error Code: E1

Malfunction decision conditions: Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition happens four times continuously.

Error Code: E0/F4

Malfunction decision conditions: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.

DuctlessAire Air Conditioner Unit Parts
DuctlessAire Air Conditioner Unit Parts

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

LG VRF Error Codes – Multi V

  Error Codes; Indicate different types of unit failures, assist in self-diagnosis and to track the frequency of occurrence. Error codes are shown on the LED of indoor units, wired remote controller, the outdoor unit control board, and on the main screen of the LG Monitoring View (LGMV) Diagnostic Software. If two or more errors occur simultaneously, the lower error code number is displayed first. After error is resolved, the error code does not display. Error Display; The first, second, and third number on the LED indicates error number; the fourth number on LED indicates outdoor unit number. Examples: 211 = Error No. 21 on master unit, 213 = Error No. 21 on slave2 unit, Error No. 105 on master unit on compressor 1. Error Code Nomenclature Definitions; MICOM: Non-volatile memory chip where unit setup information is stored. EPROM: Non-volatile memory chip where device identification, size, and factory defined default component operating parameters are stored.   LG Multi V Erro...