DuctlessAire Air Conditioner Error Codes

 Ductlessair Mini Split AC Error Codes

DuctlessAire Air Conditioner Error Codes
DuctlessAire Air Conditioner Error Codes

Indoor Unit Error Display;

Operation lampTimer lampDisplayLED STATUS
☆ 1 timeXE0Indoor unit EEPROM parameter error
☆ 2 timesXE1Indoor / outdoor units communication error
☆ 3 timesXE2Zero-crossing signal detection error
☆ 4 timesXE3Indoor fan speed has been out of control
☆ 5 timesXE4Indoor room temperature sensor T1 open circuit or short
circuit
☆ 6 timesXE5Evaporator coil temperature sensor T2 open circuit or
short circuit
☆ 7 timesXECRefrigerant leakage detection
☆ 2 timesOF1Outdoor temperature sensor T4 open circuit or short
circuit
☆ 3 timesOF2Condenser coil temperature sensor T3 open circuit or
short circuit
☆ 4 timesOF3Compressor discharge temperature sensor T5 open
circuit or short circuit
☆ 5 timesOF4Outdoor unit EEPROM parameter error
☆ 6 timesOF5Outdoor fan speed has been out of control(only for)
☆ 1 timesP0IPM malfunction or IGBT over-strong current protection
☆ 2 timesP1Over voltage or over low voltage protection
☆ 3 timesP2High temperature protection of compressor top diagnosis
and solution(only for MS11D-21HRDN1-MN5Q1W model)
☆ 5 timesP4Inverter compressor drive error

 

Error Code: P4

Malfunction decision conditions: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.

Error Code: P2

Malfunction decision conditions: If the sampling voltage is not 5V, the LED will display the failure.

Error Code: P1

Malfunction decision conditions: An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.

Error Code: P0

Malfunction decision conditions: When the voltage signal that IPM send to compressor drive chip is abnormal, the display LED will show “P0” and AC will turn off.

Error Code: EC

Malfunction decision conditions: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.

Error Code: E5

Malfunction decision conditions: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.

Error Code: E3

Malfunction decision conditions: When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display the failure.

Error Code: E2

Malfunction decision conditions: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal.

Error Code: E1

Malfunction decision conditions: Indoor unit does not receive the feedback from outdoor unit during 110 seconds and this condition happens four times continuously.

Error Code: E0/F4

Malfunction decision conditions: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.

DuctlessAire Air Conditioner Unit Parts
DuctlessAire Air Conditioner Unit Parts

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

Innovair Air Conditioner Error Codes

 innovair  prestige  inverter mini split system: Innovair Air Conditioner Error Codes Error Codes Problem E2 Anti-freezing protection E3 Block or Low pressure of refrigerant system E4 Compressor exhaust high temperature protection E5 AC over-current protection E6 Communication failure between indoor unit and outdoor unit E8 Anti-high temperature protection H4 Anti-high temperature protection H6 No feedback of indoor fan motor C5 Jumper cap malfunction protection LP Indoor unit and outdoor unit doesn't match L3 Outdoor DC fan motor malfunction L9 Power protection Fo Gathering refrigerant F1 Indoor ambient sensor open or short circuit F2 Indoor tube sensor open or short circuit F3 Outdoor ambient sensor open or short circuit F4 Outdoor tube sensor open or short circuit F5 Exhaust sensor open or short circuit F6 Overload limit / drop frequency F8 Over current limit / drop frequency F9 High exhaust temperature limit / drop frequency F0 Refrigerant leakage protection FH Anti-f...