Actron AC Error Codes and Troubleshooting

 

Actron AC Error Codes and Troubleshooting
Actron AC Error Codes and Troubleshooting

In the unlikely event that a fault develops with the Air Conditioner the microprocessor will diagnose the fault (where possible) and display a fault code on the wall controller. The 7 Day Controller will display a code beginning with E (Eg E2) The 24 Hr Controller will display:

  1. single digit number (eg 9)
  2. the heat and cool indicators flashing simultaneously
  3. both codes showing together

Take note of the fault code and contact your installer. This code will indicate to the installer/repairer what the problem may be.

Error CodesProblem
E1Outdoor coil sensor open or closed circuit
E2Fault indoor coil out sensor
E3Fault room sensor
E4Fault indoor coil sensor
E5Communication error between outdoor and indoor
E6Fault Discharge temperature
E7Fault outdoor coil sensor
E8Fault outdoor discharge sensor
E9High or Low Pressure/Phase error

E3: System has detected less than 2 sensor ( Ultima requires at least 2 sensors in circuit) or, a remote sensor is short circuit.

E5: No Communication. The system is constantly relaying information back and forth. This indicates the communication is not happening. Contact your installer to check your wiring and cable’s integrity

M Series (AM24 and AM7) Controller Error Fault Codes
M Series (AM24 and AM7) Controller Error Fault Codes
C Series (C7-1) Controller Error Fault Codes
C Series (C7-1) Controller Error Fault Codes
Actron air fault codes
Actron air fault codes
Actron AC ESP Unit Error Fault Codes
Actron AC ESP Unit Error Fault Codes

Actron AC Remote Control Display

Actron AC Remote Control Display
Actron AC Remote Control Display

Actron AC System Control Alarm Mix

Actron AC System Control Alarm Mix
Actron AC System Control Alarm Mix

Actron AC Troubleshooting

Conditions: The system does not start.

Remedy:

  • Check that 5 minutes has passed from the time you turned the system on as there are in-built safety timers.
  • Check thermostat settings are correct.
  • Check thermostat set point is low enough for cooling or high enough for heating.
  • Check the Master Controller is set to the correct mode for COOL/AUTO/HEAT.

Conditions: Air does not flow.

Remedy:

  • Check if the unit is set in the correct mode COOL/AUTO/HEAT.
  • Check your zone control is turned on. If using sensor ensure your zone is on at the master.
  • During defrost cycle of the outdoor unit in heating mode, the indoor fan will not operate. Defrost cycle is indicated when the heat LED on the master control is flashing.

Conditions: OFF is displayed on my zone control and I can not turn it on.

Remedy: This means the Master Controller is turned off. First turn on your air conditioner at the master control. You will now be able to turn on your zone control.

 

Frequently Asked Questions

1- I can not adjust my set point on my zone controller any more than 2 degrees higher or lower than the master controller.

-2 degrees is the the default setting for master temperature offset. ActronAir recommend this 2 degree offset to optimise temperature control and maximize energy efficiency. Moving this settings outside +/-2 degrees will result in temperature inaccuracy

2- Cooling and Heating seems to take a long time to achieve temperature in ESP fan mode. Am I using the correct settings?

-ESP fan mode really comes into it’s own when minimal zones are used. For quicker and more responsive Cooling and Heating when using more than minimal zones, select High or Cont High fan speed on the master control. This will boost heating and cooling and is best optimized when you want to condition more than the minimal zone set up.

3- Cooling and Heating is not sufficient in my zone.

-Air balancing is essential part of system commissioning in Ultima system. The duct design may be prohibiting the correct amount of airflow reaching your area. Please contact your installer to ensure air balancing has been carried out.

4– There is substantial air noise coming from my outlet.

-If the outlet gets too noisy when the unit or zone is first turned on, the system maybe over supplying airflow to your area. Ensure ESP fan mode is used when using minimal zones.Please contact your installer to ensure air balancing has been carried out.

5- There are dashes across my control display

-Make sure you have not had a power cut out. If this is still present on the display after 20 seconds, please contact your installer. Incorrect wiring or a broken circuit could also cause these symptoms

Actron AC Manual Pdf

Actron AC Troubleshooting – Error Fault Codes PDF

Reference: www.actronair.com.au

Comments

Popular posts from this blog

Rittal Air Conditioner Error Codes

  System messages are shown on the display screen of the Comfort controller via the displays A1 to A20 and E0. Rittal Air Conditioner Error Codes Error Codes System message Possible cause A1 Enclosure door open Door open or door limit switch incorrectly positioned A2 Internal temperature of enclosure too high Cooling capacity inadequate/unit undersized. Error as a consequence of messages A03 to A17. A3 Filter monitoring Filter mat soiled A4 Ambient temperature too high/too low Ambient temperature outside of admissible operating range (+10°C to +60°C) A5 Icing hazard Operational display in case of icing hazard. A6 PSAH pressure-operated switch Ambient temperature too high A7 Evaporator coil Lack of coolant; sensor in front of or behind condenser defective. A8 Condensate warning Condensate discharge kinked or blocked A9 Condenser fan blocked or defective Blocked or defective A10 Evaporator fan blocked or defective Blocked or defective A11 Compressor Compressor overloaded A12 Condense...

Midea VRF Error Codes

  R410A All DC Inverter V4 Plus R Series 50/60Hz Error Codes: V4 VRF:  Advanced 3-pipe technology enables  heat recovery  between indoor units for unprecedented economy and performance. It can simultaneously operate in cooling and heating mode when it is necessary to provide more freedom for operation. It compensates and adjusts when there are hot and cold rooms in the same building, depending on the direction of sunshine. As a result, it reduces annual power consumption. Midea VRF Error Codes Error Codes Problem E0 Communication error between outdoor units. Only display on the faulty slave unit, all the ODUs are in standby. E1 Phase sequence error. Display on the faulty unit, all the ODUs are in standby. E2 Communication error between indoors and the master unit. Only display on the master unit, all the ODUs are in standby. E4 Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error. Display on the faulty unit, all the ODUs are in ...

York Chiller Error Codes and Troubleshooting

  Real Time Error Numbers York Chiller Error Codes and Troubleshooting Error Description 0 All Ok 1 Datum Type Ok Test Failed 2 English Text Too Long 3 Floating Point Exception 4 Get Packet Failed 5 Get Type Failed 6 Invalid Unit Conversion 7 Invalid Hardware Selection 8 Real Time Fault 9 Spanish Text Too Long 10 Thread Exited 11 Thread Failed 12 Thread Stalled 13 Io Board Reset 14 Bram Invalid 15 Bacnet Setup Failed Problem:  No display on panel – unit will not start Possible Cause: Main supply to control system OFF. Emergency stop device off. CB3 tripped. No supply to – T2 No 24VAC supply to power board. No +12V output from powerboard. Action: Switch on main supply if safe to do so. Check if control panel emergency stop switch and any remote emergency stop devices are in the OFF position. Turn to ON position (1) if safe to do so. Check CB3 Check 115VAC to L & 2. Check wiring from – T2 to powerboard and fuse. Replace powerboard or isolate excessive loa...